Double click on the “STB_NIP2311” gateway in the DTM browser window.
The page will take several seconds to open. Once opened, you can see the STB module with the remote input and output modules. To configure these modules you must start the "Advantys" tool by clicking on the button at the top
Click on the “DDI3725” module to configure the digital inputs.
In the "I / O Image" tab you have 16 channels which correspond to the 16 inputs of the module.
The entries are active by default, but you can add a mnemonic in the box: "User name"
.
- Analog input range
- 4 to 20 mA
- Analog input data format
- Signed (15bits + sign)
- Offset (signed or unsigned)
- No offset in the current range
- Maximum account (signed or unsigned)
- No maximum measurement
- Average
- No filter to smooth the analog measurement
- Channels management
- Activate inputs
In the "I / O Image" tab you have 4 channels which correspond to the 4 inputs of the module.
You can add a mnemonic in the box: "User caption".
- 11 discrete inputs (Information on motor start-up).
- 15 discrete outputs (11 Motor run command, 3 indicator lights and a horn)
4 analog inputs (4 sensors for rotating control of bucket loaders 1, 2, 3 and 4)
Click on the “DDO3705” module to configure the digital outputs.
In the "I / O Image" tab you have 16 channels which correspond to the 16 outputs of the module.
The outputs are active by default, but you can add a mnemonic in the box: "User label".